Drinking water installations must comply with the requirements of the TrinkwV (Drinking Water Ordinance) and the UBA evaluation guidelines. Only materials with DVGW or KTW certification are permitted. Temperature range: cold water up to 25 °C, hot water up to 60 °C.

  • DVGW certification of all components
  • Lead-free materials (limit value 10 µg/l since 2013)
  • KTW guideline for plastics
  • UBA evaluation guidelines for metallic materials
  • Water exchange at every point at least 3 times per week
  • Observe maximum stagnation time
  • Flush line if not used for >72h
  • Avoid dead legs
  • Hot water ≥60 °C at storage tank outlet (Legionella protection)
  • Regular sampling recommended

Temperaturbereich

Cold water ≤25 °C, hot water ≤60 °C (briefly 70 °C)

Druckinformation

Typically PN 10 in domestic network